Lutz-JESCO America Corporation Metering Technology That Works For You
Lutz-JESCO America Corporation
> Measuring and Control > TOPAX® Controllers > Controller TOPAX® L 2

  Select from the files and links below:
  » Instruction Manual (PDF)
  » Spec Sheet (PDF)
  » Customer Service/Technical Support

Download the free Adobe Acrobat Reader to view PDF files.
General Description

TOPAX® L 2 Controller

  • pH value measuring and controller device.
  • Temperature controller device.

    Measuring unit

  • Measures: pH value, temperature
  • Metering range:
           - 0.00 - 14.00 mg/l Cl2 - Chlorine measurement
           - -22 - 284°F - Temperature measurement
  • Display: Measurement values with relative units. Status messages, sensors. Calibration, controller and alarm.
  • Temperature compensation: Either manual or automatic, Pt 100 measuring principle.

    Controller unit

  • Switch points: 2 switch points with adjustable effective direction setting
  • Controller options: ON/OFF controller, with optional hysteresis. Proportional (P) controller - pulse-pause, pulse- frequency or continuous controller. Proportional integral (PI) controller - pulse-pause, pulse- frequency or continuous controller
  • Hysteresis: 0.00 - 14.00 pH
  • Proportional gain KP: 0.00 -14.00 pH
  • Reset time TN 0 - 2000 sec
  • Minimum impulse: 0.1 - 9.9 sec
  • Pulse + pause time: 02 - 99 sec
  • Impulse frequency: 100 - 7200 impulses/h
  • Switch-on delay: 0 - 200 sec
  • Alarm function: minimum and maximum threshold value and delay time

Lutz-JESCO America Corp. | 55 Bermar Park, Rochester, New York 14624, USA
Email Us: mail@jescoamerica.com | Phone: 585-426-0990 | Fax: 585-426-4025 | Toll Free: 800-554-2762
©2010 Lutz-JESCO America Corp. All rights reserved. Legal notices. Privacy Policy