General Description

TOPAX® L 4 Controller

  • Chlorine dioxide measuring and controller device.
  • Temperature controller device.

    Measuring unit

  • Measures: Free chlorine content, temperature
  • Metering range:
           - 0.00 - 4.00 mg/l H2O2 - Chlorine dioxide measurement
           - -22 - 284°C - Temperature measurement
  • Display: Measurement values with relative units. Status messages, sensors. Calibration, controller and alarm.
  • Temperature compensation: Either manual or automatic, Pt 100 measuring principle.

    Controller unit

  • Switch points: 2 switch points with adjustable effective direction setting
  • Controller options: ON/OFF controller, with optional hysteresis. Proportional (P) controller - pulse-pause, pulse- frequency or continuous controller. Proportional integral (PI) controller -

    pulse-pause, pulse- frequency or continuous controller

  • Hysteresis: freely adjustable within the metering range
  • Proportional gain KP: freely adjustable within the metering range
  • Reset time TN 0 - 2000 sec
  • Minimum impulse: 0.1 - 9.9 sec
  • Pulse + pause time: 02 - 99 sec
  • Impulse frequency: 100 - 7200 impulses/h
  • Switch-on delay: 0 - 200 sec
  • Alarm function: minimum and maximum threshold